Virginia Administrative Code (Last Updated: January 10, 2017) |
Title 9. Environment |
Agency 5. State Air Pollution Control Board |
Chapter 40. Existing Stationary Sources |
Section 7980. Standard for carbon monoxide
-
No owner or other person shall cause or permit to be discharged into the atmosphere from any affected facility any gases that contain carbon monoxide in excess of the following limits:
1. For mass burn waterwall units: 100 parts per million by volume, corrected to 7.0% oxygen, dry basis, calculated as an arithmetic average (four-hour average).
2. For mass burn refractory units: 100 parts per million by volume, corrected to 7.0% oxygen, dry basis, calculated as an arithmetic average (four-hour average).
3. For mass burn rotary refractory units: 100 parts per million by volume, corrected to 7.0% oxygen, dry basis, calculated as an arithmetic average (24-hour average).
4. For mass burn rotary waterwall units: 250 parts per million by volume, corrected to 7.0% oxygen, dry basis, calculated as an arithmetic average (24-hour average).
5. For modular starved air units: 50 parts per million by volume, corrected to 7.0% oxygen, dry basis, calculated as an arithmetic average (four-hour average).
6. For modular excess air units: 50 parts per million by volume, corrected to 7.0% oxygen, dry basis, calculated as an arithmetic average (four-hour average).
7. For refuse-derived fuel stokers: 200 parts per million by volume, corrected to 7.0% oxygen, dry basis, calculated as an arithmetic average (24-hour average).
8. For bubbling fluidized bed combustors: 100 parts per million by volume, corrected to 7.0% oxygen, dry basis, calculated as an arithmetic average (four-hour average).
9. For circulating fluidized bed combustors: 100 parts per million by volume, corrected to 7.0% oxygen, dry basis, calculated as an arithmetic average (four-hour average).
10. For pulverized coal/refuse-derived fuel mixed fuel-fired combustors: 150 parts per million by volume, corrected to 7.0% oxygen, dry basis, calculated as an arithmetic average (four-hour average).
11. For spreader stoker coal/refuse-derived fuel mixed fuel-fired combustors: 200 parts per million by volume, corrected to 7.0% oxygen, dry basis, calculated as an arithmetic average (24-hour average).
Historical Notes
Derived from Volume 15, Issue 21, eff. August 4, 1999.
Statutory Authority
§ 10.1-1308 of the Code of Virginia.