Section 960. Influent and effluent sampling  


Latest version.
  • A. Sampling tests and frequency. Table C lists the typical recommended minimum sampling program schedules for all sewage treatment works (STW).

    B. STW effluent tests and frequency of effluent testing and frequency of other sampling for a treatment works will be provided in the VPDES permit or the VPA permit.

    TABLE C. TYPICAL SAMPLING PROGRAMS FOR SEWAGE TREATMENT WORKS.

    PLANT SIZE

    >2.01 MGD

    1.0-2.0 MGD

    0.101-0.999 MGD

    0.401-0.1 MGD

    0.0011-0.04 MGD

    Flow

    Totalizing, Indicating & Recording

    Totalizing, Indicating & Recording

    Totalizing, Indicating & Recording

    Totalizing, Indicating & Recording

    Estimate

    BOD5, TSS, TKN

    24- HC
    1/ Day

    24- HC
    5 Days/ Wk

    8-HC
    3 Days/ Wk

    4-HC
    1 Day/ Wk

    Grab
    1/month

    Total Nitrogen* Total Phosphorus*

    24- HC
    1/ Week

    24- HC
    1/ Week

    8-HC
    1/ 2 Weeks

    4-HC
    1/ Month

    Grab
    1/month

    TRC, Contact tank**

    Grab 1/2 Hr

    4/Day at 4 Hr.Intervals

    3/Day at 4 Hr.Intervals

    3/Day at 4 Hr.Intervals

    Grab
    1/Day

    Fecal Coliform**

    Grab
    1/Day
    10am-4pm

    Grab
    5 Days/Wk
    10am-4pm

    Grab
    3 Days/Wk
    10am-4pm

    Grab
    1/Week
    10am-4pm

    Grab
    1/Month
    10am-4pm

    pH, DO, TRC Effluent

    Grab
    1/Day

    Grab
    1/Day

    Grab
    1/Day

    Grab
    1/Day

    Grab
    1/Day

    WQS Parameters (Toxics)

    1/8,24 HC or 1/month

    1/8,24 HC or 1/month

    1/8, 8HC or 1/month

    1/8, 4HC or 1/month

    Grab
    1/month

Historical Notes

Former 12VAC5-581-1020 derived from Volume 18, Issue 10, eff. February 27, 2002; amended and adopted as 9VAC25-790-960, Virginia Register Volume 20, Issue 09, eff. February 12, 2004.

Statutory Authority

§ 62.1-44.19 of the Code of Virginia.