Virginia Administrative Code (Last Updated: January 10, 2017) |
Title 9. Environment |
Agency 25. State Water Control Board |
Chapter 580. Underground Storage Tanks: Technical Standards and Corrective Actionrequirements |
Section 70. Notification requirements
-
A. Any owner who brings an underground storage tank system into use after May 8, 1986, must within 30 days of bringing such tank into use, submit, in the form prescribed in APPENDIX I of this chapter, a notice of existence of such tank system to the board. Any change in ownership, tank status (e.g., temporarily/permanently closed out), tank/piping systems (e.g., upgrades such as addition of corrosion protection, internal lining, release detection), substance stored (e.g., change from petroleum to hazardous substance) requires the UST owner to submit an amended notification form within 30 days after such change/upgrade occurs or is brought into use. Owners may provide notice for several tanks using one notification form, but owners with tanks located at more than one place of operation must file a separate notification form for each separate place of operation.
B. Under Virginia UST notification requirements effective July 1, 1987, owners of property who have actual knowledge of underground storage tanks on such property that were taken out of service before January 1, 1974, yet still in the ground, must notify the board on the notification form.
NOTE: Under the federal UST Notification Program, owners and operators of UST systems that were in the ground on or after May 8, 1986, unless taken out of operation on or before January 1, 1974, were required to notify the board in accordance with the Hazardous and Solid Waste Amendments of 1984, P.L. 98-616 (42 USC § 9603), on a form published by EPA on November 8, 1985, (50 FR 46602) unless notice was given pursuant to § 103(c) of CERCLA. Owners and operators who have not complied with the notification requirements may use portions I through VI of the notification form contained in APPENDIX I of this chapter.
C. Notices required to be submitted under subsection A of this section must provide all of the information in Sections I through VI of the prescribed form (APPENDIX I) for each tank for which notice must be given. Notices for tanks installed after December 22, 1988, must also provide all of the information in Section VII of the prescribed form (APPENDIX I) for each tank for which notice must be given.
D. All owners and operators of new UST systems must certify in the notification form compliance with the following requirements:
1. Installation of tanks and piping under subsection 5 of 9VAC25-580-50;
2. Cathodic protection of steel tanks and piping under subsections 1 and 2 of 9VAC25-580-50;
3. Financial responsibility under financial responsibility regulations promulgated by the board.
4. Release detection under 9VAC25-580-140 and 9VAC25-580-150.
E. All owners and operators of new UST systems must ensure that the installer certifies in the notification form that the methods used to install the tanks and piping comply with the requirements in subsection 4 of 9VAC25-580-50.
F. Beginning October 24, 1988, any person who sells a tank intended to be used as an underground storage tank must notify the purchaser of such tank of the owner's notification obligations under subsection A of this section. The statement provided in APPENDIX II of this chapter may be used to comply with this requirement.
Historical Notes
Derived from VR680-13-02 § 2.3, eff. October 25, 1989.
Statutory Authority
§§ 62.1-44.15(10) and 62.1-44.34:9 of the Code of Virginia.