Section 420. Artificial light and climate control
Latest version.
-
A. Artificial light shall be provided in all rooms to provide an average illumination of six foot-candles over the area of the room and at least 20 foot-candles at desk level and in personal grooming areas.
B. Heat and air conditioning or mechanical ventilation shall be evenly distributed in all rooms so that a temperature not less than 65°F nor more than 85°F is maintained. Air conditioning or mechanical ventilating systems shall be provided to maintain temperatures of not more than 85°F.