Section 298. Chapter 26 Plastic  


Latest version.
  • Change Section 2603.5.5 of the IBC to read:

    2603.5.5 Vertical and lateral fire propagation. Exterior wall assemblies shall be tested in accordance with, and comply with, acceptance criteria of NFPA 285. Where noncombustible materials or combustible materials permitted by Sections 603, 803, 806 or 1406 differ from assembly to assembly or within an assembly, multiple tests shall not be required.

    Exception: Exterior wall assemblies are not required to be tested in accordance with, and comply with, acceptance criteria of NFPA 285 where any of the following conditions are met:

    1. One-story buildings complying with Section 2603.4.1.4.

    2. Wall assemblies where the foam plastic insulation is covered on each face by a minimum of 1-inch (25 mm) thickness of masonry or concrete complying with either of the following:

    2.1. There is no air space between the insulation and the concrete or masonry; or

    2.2. The insulation has a flame spread index of not more than 25 as determined in accordance with ASTM E 84 or UL 723 and the maximum air space between the insulation and the concrete or masonry is not more than 1 inch (25 mm).

    3. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.

Historical Notes

Derived from Volume 30, Issue 16, eff. July 14, 2014.