Section 235. Chapter 8 Interior finishes  


Latest version.
  • Change Section 806.1.2 of the IBC to read:

    806.1.2 Combustible decorative materials. The permissible amount of decorative materials meeting the flame propagation performance criteria of NFPA 701 shall not exceed 10% of the specific wall or ceiling area to which it is attached.

    Exceptions:

    1. In auditoriums or similar types of spaces in Group A, the permissible amount of decorative material meeting the flame propagation performance criteria of NFPA 701 shall not exceed 75% of the aggregate wall area where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 and where the material is installed in accordance with Section 803.11.

    2. In auditoriums or similar types of spaces in Group A, the permissible amount of decorative materials suspended from the ceiling, located no more than 12 inches (305 mm) from the wall, not supported by the floor, and meeting the flame propagation performance criteria of NFPA 701, shall not exceed 75% of the aggregate wall area when the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.

    3. The amount of fabric partitions suspended from the ceiling and not supported by the floor in Groups B and M occupancies shall not be limited.

Historical Notes

Derived from Volume 30, Issue 16, eff. July 14, 2014.

Statutory Authority

§ 36-98 of the Code of Virginia.