Section 154. IFC Chapter 61. Liquefied Petroleum Gases  


Latest version.
  • A. Change Section 6101.2 to read:

    6101.2. Permits. Permits shall be required as set forth in Section 107.2. Distributors shall not fill an LP-gas container for which a permit is required unless a permit for installation has been issued for that location by the fire code official, except when the container is for temporary use on construction sites.

    B. Add Section 6106.4 to read:

    6106.4. DOTn cylinders filled on site. DOTn cylinders in stationary service that are filled on site and therefore are not under the jurisdiction of DOTn either shall be requalified in accordance with DOTn requirements or shall be visually inspected within 12 years of the date of manufacture or within five years from May 1, 2008, whichever is later, and within every five years thereafter, in accordance with the following:

    1. Any cylinder that fails one or more of the criteria in Item 3 shall not be refilled or continued in service until the condition is corrected.

    2. Personnel shall be trained and qualified to perform inspections.

    3. Visual inspection shall be performed in accordance with the following:

    3.1. The cylinder is checked for exposure to fire, dents, cuts, digs, gouges, and corrosion according to CGA C-6, Standards for Visual Inspection of Steel Compressed Gas Cylinders, except that paragraph 4.2.1(1) of that standard (which requires tare weight certification), shall not be part of the required inspection criteria.

    3.2. The cylinder protective collar (where utilized) and the foot ring are intact and are firmly attached.

    3.3. The cylinder is painted or coated to retard corrosion.

    3.4. The cylinder pressure relief valve indicates no visible damage, corrosion of operating components, or obstructions.

    3.5. There is no leakage from the cylinder or its appurtenances that is detectable without the use of instruments.

    3.6. The cylinder is installed on a firm foundation and is not in contact with the soil.

    3.7. A cylinder that passed the visual inspection shall be marked with the month and year of the examination followed by the letter "E" (example: 10-01E, indicating requalification in October 2001 by the external inspection method).

    3.8. The results of the visual inspection shall be documented, and a record of the inspection shall be retained for a five-year period.

    Exception: Any inspection procedure outlined in Items 3.1 through 3.8 that would require a cylinder be moved in such a manner that disconnection from the piping system would be necessary shall be omitted, provided the other inspection results do not indicate further inspection is warranted.

    C. Change Section 6111.2 to read:

    6111.2. Unattended parking. The unattended parking of LP-gas tank vehicles shall be in accordance with Sections 6111.2.1 and 6111.2.2.

    Exception: The unattended outdoor parking of LP-gas tank vehicles may also be in accordance with Section 9.7.2 of NFPA 58.

Historical Notes

Derived from Volume 22, Issue 03, eff. November 16, 2005; amended, Virginia Register Volume 24, Issue 14, eff. May 1, 2008; Volume 27, Issue 02, eff. March 1, 2011; Change in Effective Date, 27:5 VA.R. 533 November 8, 2010; amended, Virginia Register Volume 30, Issue 16, eff. July 14, 2014.

Statutory Authority

§ 27-97 of the Code of Virginia.