Section 540. Chapter 6 Mechanical and electrical requirements  


Latest version.
  • A. Change Section 602 of the IPMC to read:

    Section 602 Heating and Cooling Facilities.

    B. Change Section 602.1 of the IPMC to read:

    602.1 Facilities required. Heating and cooling facilities shall be maintained and operated in structures as required by this section.

    C. Change Section 602.2 of the IPMC to read:

    602.2 Heat supply. Every owner and operator of a Group R-2 apartment building or other residential dwelling who rents, leases or lets one or more dwelling unit, rooming unit, dormitory or guestroom on terms, either expressed or implied, to furnish heat to the occupants thereof shall supply heat during the period from October 15 to May 1 to maintain a temperature of not less than 65°F (18°C) in all habitable rooms, bathrooms, and toilet rooms. The code official may also consider modifications as provided in Section 104.5.2 when requested for unusual circumstances or may issue notice approving building owners to convert shared heating and cooling piping HVAC systems 14 calendar days before or after the established dates when extended periods of unusual temperatures merit modifying these dates.

    Exception: When the outdoor temperature is below the winter outdoor design temperature for the locality, maintenance of the minimum room temperature shall not be required provided that the heating system is operating at its full design capacity. The winter outdoor design temperature for the locality shall be as indicated in Appendix D of the IPC.

    D. Add Section 602.2.1 to the IPMC to read:

    602.2.1 Prohibited use. In dwelling units subject to Section 602.2, one or more unvented room heaters shall not be used as the sole source of comfort heat in a dwelling unit.

    E. Change Section 602.3 of the IPMC to read:

    602.3 Occupiable work spaces. Indoor occupiable work spaces shall be supplied with heat during the period from October 1 to May 15 to maintain a temperature of not less than 65°F (18°C) during the period the spaces are occupied.

    Exceptions:

    1. Processing, storage and operation areas that require cooling or special temperature conditions.

    2. Areas in which persons are primarily engaged in vigorous physical activities.

    F. Change Section 602.4 of the IPMC to read:

    602.4 Cooling supply. Every owner and operator of a Group R-2 apartment building who rents, leases or lets one or more dwelling units, rooming units or guestrooms on terms, either expressed or implied, to furnish cooling to the occupants thereof shall supply cooling during the period from May 15 to October 1 to maintain a temperature of not more than 80°F (27°C) in all habitable rooms. The code official may also consider modifications as provided in Section 104.5.2 when requested for unusual circumstances or may issue notice approving building owners to convert shared heating and cooling piping HVAC systems 14 calendar days before or after the established dates when extended periods of unusual temperatures merit modifying these dates.

    Exception: When the outdoor temperature is higher than the summer design temperature for the locality, maintenance of the room temperature shall not be required provided that the cooling system is operating at its full design capacity. The summer outdoor design temperature for the locality shall be as indicated in the IECC.

    G. Change the exception to Section 604.3.1.1 of the IPMC to read:

    Exception: The following equipment shall be allowed to be repaired or reused where an inspection report from the equipment manufacturer, an approved representative of the equipment manufacturer, a third party licensed or certified electrician, or an electrical engineer indicates that the exposed equipment has not sustained damage that requires replacement:

    1. Enclosed switches, rated 600 volts or less;

    2. Busway, rated 600 volts or less;

    3. Panelboards, rated 600 volts or less;

    4. Switchboards, rated 600 volts or less;

    5. Fire pump controllers, rated 600 volts or less;

    6. Manual and magnetic motor controllers;

    7. Motor control centers;

    8. Alternating current high-voltage circuit breakers;

    9. Low-voltage power circuit breakers;

    10. Protective relays, meters and current transformers;

    11. Low-voltage and medium-voltage switchgear;

    12. Liquid-filled transformers;

    13. Cast-resin transformers;

    14. Wire or cable that is suitable for wet locations and whose ends have not been exposed to water;

    15. Wire or cable, not containing fillers, that is suitable for wet locations and whose ends have not been exposed to water;

    16. Luminaires that are listed as submersible;

    17. Motors;

    18. Electronic control, signaling and communication equipment.

    H. Change Section 606.1 to the IPMC to read:

    606.1 General. Elevators, dumbwaiters and escalators shall be maintained in compliance with ASME A17.1. The most current certificate of inspection shall be on display at all times within the elevator or attached to the escalator or dumbwaiter, be available for public inspection in the office of the building operator or be posted in a publicly conspicuous location approved by the code official. An annual periodic inspection and test is required of elevators and escalators. A locality shall be permitted to require a six-month periodic inspection and test. All periodic inspections shall be performed in accordance with Section 8.11 of ASME A17.1. The code official may also provide for such inspection by an approved agency or through agreement with other local certified elevator inspectors. An approved agency includes any individual, partnership or corporation who has met the certification requirements established by the VCS.

Historical Notes

Derived from Volume 22, Issue 03, eff. November 16, 2005; amended, Virginia Register Volume 27, Issue 02, eff. March 1, 2011; Change in Effective Date, 27:5 VA.R. 534 November 8, 2010; amended, Virginia Register Volume 30, Issue 16, eff. July 14, 2014.

Statutory Authority

§ 36-98 of the Code of Virginia.