Section 133. IFC Chapter 5. Fire Service Features  


Latest version.
  • A. Change Section 501.2 to read:

    501.2. Permits. A permit shall be required as set forth in Section 107.2.

    B. Delete Section 501.4.

    C. Add exceptions to Section 503.1 to read:

    Exceptions:

    1. Fire apparatus access roads shall be permitted to be provided and maintained in accordance with written policy that establish fire apparatus access road requirements and such requirements shall be identified to the owner or his agent prior to the building official's approval of the building permit.

    2. On construction and demolition sites fire apparatus access roads shall be permitted to be provided and maintained in accordance with Section 3310.1.

    D. Add exception to Section 503.2.1 to read:

    Exception: Fire apparatus access roads exclusively serving single family dwelling or townhouse developments that are fully sprinklered as provided for in Sections R313.1 or R313.2 of the International Residential Code shall have an unobstructed width of not less than 18 feet (5486 mm), exclusive of shoulders.

    E. Add Section 503.7 to read:

    503.7. Fire lanes for existing buildings. The fire code official is authorized to designate public and private fire lanes as deemed necessary for the efficient and effective operation of fire apparatus. Fire lanes shall comply with Sections 503.2 through 503.6.

    F. Add Sections 507.3.1 and 507.3.2 to read:

    507.3.1. Fire flow requirements for fully sprinklered residential developments. Notwithstanding Section 103.1.2, the fire flow requirements in Table B105.1 of Appendix B of the IFC, as modified by Section 507.3.2, shall be permitted to be used for determining fire flow in single family dwelling and townhouse developments which are fully sprinklered as provided for in Sections R313.1 or R313.2 of the International Residential Code.

    507.3.2. Modifications to Table B105.1. The first six rows of columns five and six of Table B105.1 of Appendix B of the IFC shall be modified as shown below for the use of Table B105.1 in Section 507.3.1.

    Type 5-B

    Fire-flow
    (gallons per minute)

    0-5000

    1000

    5001-7200

    1250

    7201-8200

    1500

    8201-9500

    1750

    9501-11300

    2000

    11301-13000

    2250

    G. Change Section 507.5.1 to read:

    507.5.1. Where required. Fire hydrant systems shall be located and installed as directed by the fire department. Fire hydrant systems shall conform to the written standards of the jurisdiction and the fire department.

    H. Add Section 507.5.1.2 to read:

    507.5.1.2. Fire hydrant requirements for fully sprinklered residential developments. Notwithstanding Section 103.1.2, the number and distribution of fire hydrants in Table C105.1 of Appendix C of the IFC shall be permitted to be used in single family dwelling and townhouse developments which are fully sprinklered as provided for in Sections R313.1 or R313.2 of the International Residential Code, with the spacing and distances of fire hydrants indicated in Table C105.1 increased by 100%.

    I. Change Section 510 to read:

    Section 510.
    Maintenance of In-Building Emergency Communication Equipment.

    510.1. General. In-building emergency communication equipment shall be maintained in accordance with USBC and the provisions of this section.

    510.2. Additional in-building emergency communications installations. If it is determined by the locality that increased amplification of their emergency communication system is needed, the building owner shall allow the locality access as well as provide appropriate space within the building to install and maintain necessary additional communication equipment by the locality. If the building owner denies the locality access or appropriate space, or both, the building owner shall be responsible for the installation and maintenance of these additional systems.

    510.3. Field tests. After providing reasonable notice to the owner or their representative, the fire official, police chief, or their agents shall have the right during normal business hours, or other mutually agreed upon time, to enter onto the property to conduct field tests to verify that the required level of radio coverage is present at no cost to the owner.

Historical Notes

Derived from Volume 16, Issue 20, eff. September 15, 2000; amended, Virginia Register Volume 19, Issue 25, eff. October 1, 2003; Errata, 20:1 VA.R. 39 September 22, 2003; amended, Virginia Register Volume 22, Issue 03, eff. November 16, 2005; Volume 24, Issue 14, eff. May 1, 2008; Volume 27, Issue 02, eff. March 1, 2011; Change in Effective Date, 27:5 VA.R. 533 November 8, 2010; amended, Virginia Register Volume 27, Issue 12, eff. March 1, 2011; Volume 30, Issue 16, eff. July 14, 2014.

Statutory Authority

§ 27-97 of the Code of Virginia.