Section 1160. Valve, air relief, meter, and blowoff chambers  


Latest version.
  • A. Air and sediment accumulations may be removed through a standard fire hydrant; compressed air and pumping may be used for dewatering mains through hydrants.

    B. Chambers or pits containing valves, blowoffs, meters, or other such appurtenances to a distribution system shall not be connected directly to any storm drain or sanitary sewer, nor shall blowoffs or air relief valves be connected directly to any sewer.

    C. Such chambers or pits shall be drained to the surface of the ground where they are not subject to flooding by surface water or to absorption pits located above the seasonal groundwater table elevation. Sump pumps may be used where other means are not practicable.

    D. The open end of an air relief pipe shall be extended from the manhole or enclosing chamber to a point at least one foot above ground and provided with a screened, downward facing elbow.

Historical Notes

Derived from VR355-18-012.06 § 3.53, eff. August 1, 1991.

Statutory Authority

§ 32.1-12 and 32.1-170 of the Code of Virginia.