Section 1000. Disinfection  


Latest version.
  • A. Objective. To prevent the occurrence of waterborne diseases from consumption of drinking water.

    B. Methods. Disinfection shall be accomplished by the application of chlorine. The specific chlorine compound shall be selected on the basis of water flow rates, application rates, pH of the water, cost of equipment and chemicals, availability of disinfectant, and reliability of feed equipment. Alternate chemicals and methods for disinfection are to be handled as unconventional and the procedures of 12VAC5-590-300 apply.

    C. Equipment.

    1. Solution feed vacuum type gas chlorinators are generally preferred. The use of hypochlorite feeders of the positive displacement type may be considered for small installations.

    2. Chlorinator capacities will vary, depending on the use and point of application of the chlorine and the raw water quality. Chlorination capacity shall be such that a minimum dosage of 15 milligrams per liter may be fed at all times.

    3. Standby chlorination equipment shall be provided and chlorination capacities shall comply with 12VAC5-590-1000 C 2 with any unit out of operation for repairs. Spare parts shall be available for all chlorinators to replace parts which are subject to wear and breakage. All chlorinators shall be properly maintained and operated.

    4. An ample supply of potable water shall be available for operating the chlorinator. Where a booster pump is required, duplicate equipment shall be provided, and, when necessary, standby power as well. Equipment for backflow prevention shall be provided. A pressure gauge shall be provided on each chlorinator water supply line.

    5. Scales for weighing cylinders shall be provided at all waterworks using chlorine gas. At large waterworks, scales of the indicating and recording type are recommended. Scales shall be recessed unless they are of the low platform type.

    6. Where manifolding of several cylinders is required to evaporate sufficient chlorine, consideration shall be given to the installation of gas evaporators.

    7. A bottle of ammonia hydroxide solution shall be available for detecting chlorine gas leaks. Consideration shall also be given to the provision of caustic soda solution reaction tanks for absorbing the contents of leaking one-ton cylinders where such cylinders are in use. At large installations, consideration should be given to the installation of automatic gas detection and related alarm equipment. Emergency cylinder repair kits shall be provided.

    8. Piping and connections for chlorine gas.

    a. Piping arrangements should be as simple as possible. Pressure gauges shall be installed on the piping to each chlorinator. The number of screwed or flanged joints should be held to a minimum. Piping systems should be well supported and adequately sloped to allow drainage; low spots should be avoided. Suitable allowance should be provided for pipe expansion due to changes in temperature. Liquid chlorine has a high coefficient of thermal expansion. If liquid chlorine (containing no gas bubbles) is trapped between two valves, high pressure will develop upon increase in the temperature of the chlorine. This pressure may lead to hydrostatic rupture of the line. The effects of possible rupture should be considered in the design of any piping system. Where such rupture would present an undue hazard to personnel or equipment by allowing large quantities of chlorine to escape, protection of the system against hydrostatic pressure should be provided.

    b. Condensation or reliquefaction of chlorine may occur in chlorine gas lines which pass through areas where the temperature is below the temperature pressure equilibrium indicated in the vapor pressure curve. Where adequate superheat is not provided by a vaporizer, condensation can be prevented by reducing the pressure with a pressure reducing valve.

    c. It is recommended that joints in chlorine piping be flanged or welded. If threaded joints are used, extreme care should be taken to obtain clean, sharp threads. A lubricating pipe dope suitable for chlorine should be used. All threading oil must be thoroughly cleaned from the pipe. For permanent joints, linseed oil and graphite, glycerine or Teflon tape may be used. If Teflon tape is used, all remnants must be removed before joints are remade.

    d. Fittings and appurtenances must be suitable for handling dry chlorine.

    9. Chlorine solution is very corrosive to all of the common construction metals. At low pressures, chlorine solution can be handled in chemical stoneware, glass or porcelain equipment, and by certain alloys. Hard rubber, unplasticized polyvinylchloride, glassfiber reinforced polyester, polyvinylidene chloride, and fully halogenated fluorocarbon resins have been used successfully. Low molecular weight polyethylene, fiber reinforced rubber hose, and wrapped rubber hose have been used successfully for small capacity chlorinators. All of these materials must be selected with great care. For higher pressures, combinations using resistant lining materials (rubber, kynar, saran, Teflon, etc.) with the common metals for strength should be used.

    Titanium may be used with chlorine solution, but must not be used with chlorine gas. Tantalum is inert to chlorine solution at temperatures up to 300°F. Hastelloy Alloy C® and Monel Alloy® are widely used. Platinum and silver find special applications. In general, operations involving chlorine solution require individual study.

    Chlorine and equipment suppliers shall make recommendations only after careful survey of all factors involved.

    10. Chlorine solution and hypochlorite solution piping shall be arranged such that prechlorination or postchlorination may be accomplished by any or all chlorinators.

    D. Engineering design.

    1. Any building to house chlorine equipment or containers should be designed and constructed to protect all elements of the chlorine system from fire hazards. If flammable materials are stored or processed in the same building, a fire wall should be erected to separate the two areas. Fire resistive construction is recommended.

    If gas chlorination equipment and chlorine cylinders are to be in a building used for other purposes, a gas tight partition shall separate this room from any other portion of the building. Doors to this room shall open only to the outside of the building, and shall be equipped with panic hardware. Such rooms shall be at ground level, and should be separated from the feed area.

    At least two means of exit should be considered from each separate room or building in which chlorine is stored, handled, or used. All exit doors shall open outward.

    A clear glass, gas tight window shall be installed in an interior wall of the chlorinator room to permit the chlorinators to be viewed without entering the room.

    Feed lines shall not carry chlorine gas beyond the chlorine feeder room unless the chlorine is under vacuum.

    2. Chlorinator rooms shall be provided with a means of heating so that a temperature of at least 60°F can be maintained, but the room should be protected from excess heat. Cylinders shall be kept at essentially room temperature for at least 24 hours prior to use unless an evaporator is employed.

    3. Forced, mechanical ventilation which will provide one complete air change per minute shall be installed in all chlorine feed rooms and rooms where chlorine cylinders are stored. The entrance to the air exhaust duct from the room shall be near the floor and the point of discharge shall be located so as not to contaminate the air inlet to any building or inhabited areas. Air inlets shall be located so as to provide cross ventilation with air and at such temperature that will not adversely affect the chlorination equipment. The vent hose shall run without traps from the chlorinator and shall discharge to the outside atmosphere above grade.

    4. The electrical controls for the fans and lights shall be such that they will automatically operate when the door is opened and can be manually operated from the outside without opening the door.

    E. Respiratory protection. The use of self-contained breathing apparatus (SCBA) in compliance with OSHA Respiratory Protection Standard 1910.134, "VIRGINIA OSHA STANDARDS" for General Industry, is required whenever anyone is dealing with an accidental release of chlorine. All waterworks that use chlorine gas at their treatment facility shall maintain a respiratory protection plan including emergency procedures, evacuation plans, designated SCBA personnel and any special site specific requirements. All respiratory protection devices shall be stored to protect against dust, sunlight, heat, extreme cold, excessive moisture or damaging chemicals; and in a location remote from the chlorine area.

    F. Application of chlorine.

    1. Provisions shall be made to ensure uniform mixing of the chlorine solution or hypochlorite solution with the water near the point of application.

    2. Residual and contact time.

    a. Waterworks with surface water sources shall provide a minimum residual (C) and contact time (T) as calculated in accordance with Appendix L. Appendix L contains information on CT calculations and methods, as well as information on contact tank baffling arrangements.

    b. Waterworks with groundwater sources shall provide a minimum 30 minute hydraulic detention period (based on design flow) for chlorine contact.

    G. Evaluation of effectiveness.

    1. Sampling - see 12VAC5-590-770.

    2. Equipment shall be provided for measuring chlorine residual employing any method listed in the most recent edition of "Standard Methods for the Examination of Water and Wastewater."

    The equipment should enable residual chlorine measurement to the nearest 0.1 milligram per liter in the range below 0.5 milligram per liter, and to an accuracy of approximately 25% above 0.5 milligram per liter. The installation of continuous automatic chlorine residual analyzers recording and proportioning systems may be required on large installations.

Historical Notes

Derived from VR355-18-009.16 § 3.37, eff. August 1, 1991; amended, Volume 09, Issue 17, eff. June 23, 1993.