Section 2270. Backflow prevention device, carbonator
Latest version.
-
A. If not provided with an air gap as specified under 12VAC5-421-2200, a double check valve with an intermediate vent preceded by a screen of not less than 100 mesh to 1 inch (100 mesh to 25.4mm) shall be installed upstream from a carbonating device and downstream from any copper in the water supply line.P
B. A dual check valve attached to the carbonator need not be of the vented type if an air gap or vented backflow prevention device has been otherwise approved as specified under subsection A of this section.