Section 870. Mixing and sedimentation  


Latest version.
  • A. Plants designed for processing surface waters shall:

    1. Provide multiple units for coagulation, flocculation, and sedimentation at plants having a rated capacity greater than 100 gallons per minute;

    2. Permit operation of flocculation basins in series or parallel;

    3. Be constructed to permit units to be taken out of service without disrupting operation; and

    4. Provide multiple stage treatment facilities when required by the division.

    B. Water containing high turbidity or coliform organisms may require pretreatment, usually sedimentation, either with or without the addition of chemicals. When pretreatment is used, the following requirements must be met:

    1. Presedimentation basins utilizing a coagulant shall have hoppered bottoms or shall be equipped with continuous sludge removal apparatus;

    2. Incoming water shall be dispersed across the full width of the line of travel as quickly as possible; short circuiting must be prevented;

    3. Provisions for bypassing sedimentation basins shall be included; and

    4. Three hours detention is the minimum period required. Greater detention may be required depending on raw water quality.

    C. Flash mixing is the rapid dispersion of chemicals throughout the water to be treated, usually by violent agitation, to enhance coagulation.

    1. Turbidity removal plants other than those of the solids contact type shall provide flash mixing facilities.

    2. Basins shall be equipped with mechanical mixing devices; other arrangements, such as baffling, may be acceptable only under special conditions. Where mechanical mixing devices are utilized, duplicate units or spare mixing equipment shall be provided.

    3. Design parameters:

    a. The detention period shall not be less than 10 seconds;

    b. The design of the flash mixing unit should be based upon the mean temporal velocity gradient G (expressed as units of seconds1). Typical values for G and T are:

    T (seconds)

    G (seconds1)

    20

    1,000

    30

    900

    40

    700

    Longer time

    790

    For optimization, the engineer should determine the appropriate G value and detention time through experimentation;

    c. The point of application of the coagulant shall be at the point of maximum mixing intensity;

    d. The physical configuration of the mixing basin shall be designed to eliminate vortexing; and

    e. Flash mix units should be designed to allow speed variation throughout at a range of one to three.

    4. Properly designed static mixers may be utilized.

    D. Flocculation mixing is the agitation of treated water at low velocity gradients for sufficient time to agglomerate coagulated particles.

    1. Basin inlet and outlet design shall prevent short circuiting and destruction of floc. A drain and overflow shall be provided. Multiple units shall be provided for continuous operability and each basin shall be designed so that individual basins may be isolated without disrupting plant operation.

    2. Design parameters:

    a. The minimum detention time shall be 30 minutes;

    b. The design of the flocculation units shall be based upon the value of GT (mean temporal velocity gradient in seconds¹) X (detention time in seconds) which is ordinarily in the range of 20,000 to 200,000. The engineer should establish the value of GT through experimentation;

    c. Variable speed drive units shall be designed to provide speed variations throughout a range of four to one;

    d. To control short circuiting in mechanical flocculators, at least three successive compartments should be provided. In addition, special attention should be given to the ports between compartments to further suppress short circuiting;

    e. To accomplish maximum power input and reduce particle shearing, tapered flocculation should be provided;

    f. In basins utilizing vertical shaft flocculators, wing walls, or stators shall be provided to prevent vortexing; and

    g. The flocculation basins must be so designed that individual basins may be isolated without disrupting plant operation.

    3. Flocculation and sedimentation basins shall be as close together as possible. The velocity gradient of the flocculated water through pipes or conduits to settling basins shall not be greater than the velocity gradient utilized in flocculating the water. Where velocity gradient is not used as a design parameter, the linear velocity in pipes and conduits from the flocculators to the settling basin shall not exceed 0.5 feet per second. Allowances must be made to minimize turbulence at bends and changes in direction.

    4. Baffling may be used to provide for flocculation in small plants only after consultation with the division. The design should be such that the velocity gradients noted above may be maintained. Turbidity removal plants other than solids contact shall provide flocculation basins.

    5. Safety. Guard rails and adequate lighting shall be provided.

    E. Sedimentation shall follow flocculation/mixing. The detention time for effective clarification is dependent upon a number of factors relating to basin design and the nature of the raw water. The number of basins required is dependent upon the plant size, turbidity, color, colloidal matter, and taste and odor causing compounds to be removed.

    1. Plants utilizing rapid rate gravity filters in conjunction with conventional sedimentation shall provide a minimum of four hours effective settling (detention) time. Effective settling time shall be calculated using the volume of the basins from the stilling wall to the submerged effluent orifice or weir.

    2. Inlets shall be designed to distribute the water equally and at uniform velocities. Open ports, submerged ports, stilling walls, and similar entrance arrangements are required. Where stilling walls are not provided, a baffle shall be constructed across the basin close to the inlet and shall project several feet below the water surface to dissipate inlet velocities and provide uniform flows across the basin.

    3. Outlet devices shall be designed to maintain velocities suitable for settling in the basin and to minimize short circuiting. The use of submerged orifices or submerged weirs is required. The maximum velocity gradient in pipes and conduits from the settling basins to the filters shall not exceed that used in flocculation. Where velocity gradient is not used as a parameter the linear velocity in pipes and conduits from settling basins shall not exceed 1.0 foot per second.

    4. Rectangular sedimentation basins should be designed with a length to width ratio of at least four to one. Surface overflow rates should be within the range of 0.25 to 0.38 gallons per minute per square foot in processes utilizing flocculation, the lower limit being utilized for cold waters and the higher limit being applied to warm waters.

    5. The circular clarifiers of the center feed, peripheral feed, and spiral flow type will be considered on an individual basis.

    6. Basins shall be provided with a means for dewatering. Basin bottoms shall slope toward the drain not less than one foot in twelve feet unless mechanical sludge collection equipment is provided.

    7. Superstructures are acceptable at specific plant locations where necessary. In areas where settling basins are subject to high and frequent cross winds, consideration should be given to the provision of windbreaks.

    8. The velocity through settling basins shall not exceed 1.0 foot per minute. The basins shall be designed to minimize short circuiting. Baffles shall be provided as necessary to minimize short circuiting.

    9. An overflow weir (or pipe) shall be installed which will establish the maximum water level desired on top of the filters. It shall discharge with a free fall at a location where the discharge will be noted.

    10. Permanent ladders or handholds shall be provided for safety on the inside walls of basins above the water level. Guard rails shall be included. Flushing lines or hydrants shall not include interconnection of the potable water with nonpotable water.

    11. For plants having a capacity of 100 gallons per minute or more, multiple basins are required and shall be so designed that individual basins may be isolated without disrupting plant operation.

    12. Mechanical sludge collecting equipment shall be considered for all plants with a capacity of 100 gallons per minute or more.

    13. Facilities are required by the State Water Control Board for disposal of sludge (see 12VAC5-590-990). Provision shall be made for the operator to observe or sample sludge being withdrawn from unit.

    F. Units that combine softening and clarification are acceptable where water characteristics are not variable and flow rates are uniform. Before solids contact units are considered as clarifiers without softening, specific approval of the division shall be obtained. Clarifiers shall be designed for the maximum uniform rate and shall be adjustable to changes in flow which are less than the design rate and for changes in water characteristics. A minimum of two units is required.

    1. A representative of the manufacturer shall supervise the installation and initial operation of each unit.

    2. The following equipment shall be provided for plant operation.

    a. Complete outfit of tools and accessories; and

    b. Adequate piping with suitable sampling taps so located as to permit the collection of samples of water from critical portions of the units.

    3. Chemical feed requirements are those listed in 12VAC5-590-860.

    4. Mixing devices shall be constructed to:

    a. Provide good mixing of the raw water with previously formed sludge particles; and

    b. Prevent deposition of solids in the mixing zone.

    5. Flocculation equipment:

    a. Shall be adjustable;

    b. Shall insure that coagulation occurs in a separate chamber or baffled zone within the unit; and

    c. Shall provide a flocculation and mixing period of at least 30 minutes.

    6. The sludge equipment shall provide either internal or external sludge concentrators in order to obtain a concentrated sludge with a minimum of waste water.

    7. Sludge removal design shall provide that:

    a. Sludge pipes shall be not less than three inches in diameter and so arranged as to facilitate cleaning;

    b. Entrance to sludge withdrawal piping will prevent clogging;

    c. Valves are located outside the tank for accessibility;

    d. The operator may observe or sample sludge being withdrawn from the unit; and

    e. A timeclock with proportional timer shall be provided for automatic blowoff.

    8. Cross connections:

    a. Blowoff outlets and drains shall terminate and discharge at a place satisfactory to the division; and

    b. Cross connection control shall be included for the potable water mains used to backflush sludge lines.

    9. The detention time shall be established on basis of the raw water characteristics and other local conditions that affect the operation of the unit. Based on design flow rates, the minimum detention time shall be:

    a. Two hours for suspended solids contact clarifiers; and

    b. One hour for the suspended solids contact softeners.

    10. Softening units should be designed so that continuous slurry concentrates of 1.0% or more, by weight, can be satisfactorily maintained.

    11. Water losses:

    a. Solids contact units shall be provided with suitable controls for sludge withdrawal;

    b. Total water losses should not exceed:

    (1) Five percent for clarifiers; and

    (2) Three percent for softening units; and

    c. The solids concentration of sludges bled to waste should be:

    (1) Three percent by weight for clarifiers,

    (2) Five percent by weight for softeners.

    12. Units used as clarifiers should be equipped with orifices. Units used for softening should be equipped with either overflow weirs or orifices. Weirs shall be:

    a. Adjustable;

    b. At least equivalent in length to the perimeter of the tank; and

    c. Constructed so that surface water does not travel over 10 feet horizontally to the collection trough.

    13. Weir loading:

    a. Weir loading shall not exceed 20 gallons per minute per foot of weir length for units used as softeners; and

    b. Orifices shall produce uniform rising rates over the entire area of the tank and shall provide for an exit velocity not to exceed 1.0 foot per second.

    14. Upflow rates shall not:

    a. Exceed 1.75 gpm/ft2 of area at the slurry separation line for units used as softeners; or

    b. Exceed 1.0 gpm/ft2 of area at the sludge separation line for units used as clarifiers.

    15. Consideration shall be given to providing a superstructure to enclose the solids contact unit, to enhance the treatment process, and for the protection of piping and associated sampling valves.

Historical Notes

Derived from VR355-18-009.03 § 3.24, eff. August 1, 1991; amended, Volume 09, Issue 17, eff. June 23, 1993.

Statutory Authority

§§ 32.1-12 and 32.1-170 of the Code of Virginia.